Analogue inputs of POWER ECU can be configured either
as:
- Logical
input
- Frequency
input
The FREQ configuration is chosen by the parameter
“Mode”.
If the input’s Mode parameter is set to
“Logical”, the input value is available for Application as a
Boolean value with the mnemonic “Input_Boo”.
The “threshold_fault”
value indicates to the Application that the input is outside the valid range,
this range is set by hardware configuration.
The fault detection is monitored by the Equipment
Variable (more details).
: It is not
possible to move to Frequency configuration while mnemonics are connected.
The input values: ON and OFF Times, are available for
application as an analogue values with the mnemonics “Input_Freq_ON”
and “Input_Freq_OFF”
respectively . These values
are given in µs. .
This is a double word variable, it must apply to the double word rule see variable rules
The “threshold_fault”
value indicates to the Application that no signal was available during a
configurable time out. This time out is set through the “Time Out”
parameter. The valid range of the “Time Out”
parameter is 0 to 25500 ms.
The fault detection is monitored by the Equipment
Variable (more details).
: It is not
possible to move to Logical configuration while mnemonics are connected.
Copyright © ACTIA 2010