Using the Actuator Test window
The actuator test supports targeted troubleshooting on the solenoid valve. Most of the troubleshooting mechanisms on the solenoid valves also work during the normal mode and can therefore detect faults without actuator test. Nevertheless, an actuator test is required. It is used to detect faults that:
- can be detected only if the solenoid valve has been energized.
- can be detected only after an OFF/ON or an ON/OFF change of the solenoid valve control.
- cannot be allocated causally and definitely during driving because several solenoid valves are switched on at the same time.
- can be detected by the audible cyclical opening when the valves are controlled individually (e.g., if a solenoid valve piston is not running smoothly).

Click Service > Actuator test in the main window. The requirements for an actuator test will be displayed. Click: OK, as soon as all requirements have been met.
 |
Click the symbol to stop communication with the transmission control unit. This function is required for debugging tasks only. |
 |
|
The following requirements must be met for an actuator test:
- Engine standstill!
- Vehicle standstill!
- Parking brake must be applied!
- Neutral position of the transmission (N key actuated)!
- Closed safety switch!
The conditions that are not met will be displayed. In principle, there are two methods of carrying out an actuator test:
- Click Auto Test. First, all solenoid valves are controlled cyclically at a frequency of 2 Hz, the controllable solenoid valves (SK, EK, DK, PB, TB and RBK) are controlled subsequently. Cyclical opening / controlling of a solenoid valve is indicated by the light green backlight and a solenoid valve symbol that is highlighted blue. If a solenoid valve malfunctions, the fault will be displayed including the fault type.

In this example, a short-circuit to ground was detected at the SK solenoid valve.
- You can also perform a targeted check of an individual solenoid valve. To do so, click the required solenoid valve. The solenoid valve is controlled cyclically with 2 Hz (2 ON/OFF changes per second) until the test is complete. This test is especially suitable for checking the smooth running of a solenoid valve piston by its audible cyclical opening. If a solenoid valve malfunctions, the fault will be displayed including the fault type.
Faults detected during an actuator test are indicated by a red "X". If a fault has occurred, carry out an upload in any case. This creates an ECU report automatically. The ECU report shows all faults that have occurred including the cause and instructions in the 'Event memory' area. For further information, please see: Upload and Report.
 |
|
The cyclical control is also required for detecting short-circuits and line interruptions in individual solenoid valves. A definite detection is not always possible during normal operation. For example, the event memory indicates short-circuits to ground for several solenoid valves. Always carry out an actuator test in such a case.
 |
Click the symbol to stop the actuator test. |
For information on the connector pin assignment for the solenoid valves at the transmission and transmission control unit, please see: Connector pin assignment.
More information on: Standard connector pin assignment
More information on: DIWA.5 assemblies
More information on:
Operational principle of the safety switch
More information on: FAQ
Up
> Higher-level section
© by Voith Turbo GmbH & Co. KG
send remarks to joachim.ehleiter@voith.com (electronic department)
or r.theilacker@voith.com (electronic department) |